How Can a Window Be Energy-Efficient and Still Cause Condensation?

A glass façade can comply with every thermal requirement, from Uw and Ucw to the energy certificate, and still show surface condensation at the glass edge and sill every January morning.

The reason is that energy performance and condensation risk are assessed with different metrics. A U-value describes the average heat flow through the whole element. Condensation risk is governed by the minimum internal surface temperature, which occurs at linear and point thermal bridges: the glass edge, the frame, the sill junction and the brackets that pass through the insulation.

This matters across our region. The Balkans combine cold continental and mountain winters with mild, humid coastal ones, while hotels, wellness centres, pools and residential towers use ever larger areas of glazing. In these conditions, condensation performance is not determined by the lowest U-value. It depends on the external design temperature, the internal humidity class and the way the building is actually operated.

Article content

So, why does a façade that passes every energy check still show condensation, and what determines whether it can be prevented?

1. The Coldest Point Decides, Not the U-Value

Condensation is a local phenomenon, while U-values are averages. A window with an excellent Uw can still have an internal surface temperature at the glass edge that falls below the dew point of the room air.

The parameter that captures this is the temperature factor, fRsi. It expresses how close the coldest internal surface stays to room temperature, on a scale from 0 (the surface is at outside temperature) to 1 (the surface is at room temperature). At 20 °C inside and −5 °C outside, a room at 50% RH has a dew point of 9.3 °C, which requires an fRsi of at least 0.57 at every point. At 60% RH, the dew point rises to 12.0 °C and the requirement to 0.68.

In most modern windows, the critical point is the edge of the insulating glass unit. The spacer and edge seal form a linear thermal bridge, described by the linear thermal transmittance Ψg. Typical default values in EN ISO 10077-1 for timber or PVC frames are around 0.08 W/mK with an aluminium spacer and around 0.05 W/mK with a thermally improved (warm-edge) spacer. The lower edge is usually the most vulnerable: the thermal bridge of the edge construction coincides there with weaker local surface heat transfer, where the frame, glazing bead and sill reduce the flow of warm room air over the glass.

Article content

Where the weak point sits depends on the frame. In a University of Utah THERM study, windows with good frames and wide thermal breaks reached the dew point first at the inside edge of the glass. With poor frames, the frame surface failed first. The same study found that windows with similar condensation-resistance ratings performed very differently under identical conditions. A full-scale test on an apartment balcony in Korea, at −15 to −20 °C outside and 50 to 65% RH inside, reached the same conclusion: the glass edge was the most sensitive point, and its low temperature was caused by heat flow through the spacer.

As an illustration, consider two windows with the same Uw of 1.4 W/m²K at 20 °C inside and −5 °C outside. In one configuration with an aluminium spacer, the glass edge may reach about 7 °C, below the 10.7 °C dew point of an apartment at 55% RH. In a comparable configuration with a warm-edge spacer, it may reach about 11 °C and stay just above it. Actual values depend on spacer material and geometry, IGU build-up, frame and thermal break, glazing rebate, installation and surface heat-transfer conditions. The point is that the same rating can hide a very different condensation result.

2. Humidity Determines the Condensation Threshold

Surface condensation has two drivers: an internal surface temperature that is too low, and an internal vapour pressure that is too high. The first is a façade design issue. The second is set by occupancy, moisture production and ventilation.

Moisture production varies strongly with activity. Indicative values published in German guidance are about 30 to 40 g/h per person at light activity, roughly half a litre per person during eight hours of sleep, and around 12 litres per day for a four-person household. Cooking, showering and drying laundry indoors add short, intense peaks on top of this background load.

Article content

The result is that every building type has its own condensation threshold. At −5 °C outside, typical design conditions give:

  • Office, 21 °C / 40% RH: vapour pressure about 1.0 kPa, dew point about 7 °C, minimum fRsi about 0.46
  • Museum or gallery, 20 °C / 50% RH: about 1.17 kPa, dew point 9.3 °C, fRsi about 0.57
  • Apartment, 20 °C / 55% RH: about 1.29 kPa, dew point 10.7 °C, fRsi about 0.63
  • Hospital ward, 22 °C / 50% RH: about 1.32 kPa, dew point about 11 °C, fRsi about 0.60
  • Restaurant kitchen, 24 °C / 60% RH: about 1.79 kPa, dew point about 16 °C, fRsi about 0.72
  • Swimming pool hall, 30 °C / 55% RH: about 2.34 kPa, dew point about 20 °C, fRsi about 0.71

The same façade product can therefore perform in an office and fail in an apartment, where the dew point is almost 4 °C higher. Humidity works in both directions: at 20 °C, a drop from 60% to 50% RH lowers the dew point by about 2.7 °C, a margin of the same order as a better glass edge.

3. Four Different Types of Condensation

“Condensation” covers four physical mechanisms. Each has a different cause and a different answer to the question “Can it be stopped?”

1. Internal surface condensation on glass, frames and sills. The internal surface temperature falls below the dew point of the room air. It can be avoided by keeping fRsi at the critical details above the building’s requirement and by controlling internal humidity.

2. External surface condensation on the outer pane. On clear, still nights, the outer pane loses heat by long-wave radiation to the sky. Pilkington’s technical guidance notes that with low-e coatings and gas-filled cavities, the outer surface can fall below the outdoor air temperature and below its dew point. The better the unit insulates, the less heat reaches the outer pane, so the risk increases as Ug decreases. It is not a defect, it is most frequent in spring and autumn, and it evaporates once the sun reaches the glass. It can be reduced, but not fully avoided without specialist glazing.

Article content

3. Condensation inside the insulating glass unit. Persistent misting in the cavity generally indicates that the edge seal has lost its integrity and the desiccant is saturated; in that case the unit has to be replaced. It is worth distinguishing this from temporary moisture or contamination on a surface, which can look similar. A frequent cause of seal failure is water standing in the glazing rebate, which degrades the perimeter sealants over time.

4. Interstitial condensation inside the façade build-up, in spandrel panels, shadow boxes and behind cladding. Warm, humid indoor air reaches cold layers through air leakage or vapour diffusion. EN ISO 13788 provides a simplified, steady-state assessment method; complex façade assemblies, with air leakage and moisture storage, may require dynamic hygrothermal simulation.

The relevant question for a project is therefore not simply “Does this façade get condensation?” It is “Which mechanism, at which point, under which design conditions?”

4. Condensation, Mould and Indoor Health

The World Health Organization’s guidelines on dampness and mould associate damp indoor environments with increased respiratory symptoms, allergies and asthma, and identify the prevention of persistent dampness on interior surfaces as the most important protective measure. Dampness and mould have been reported in 15 to 30% of European homes.

For façade design, the key point is that mould risk begins before visible condensation. EN ISO 13788 uses a surface relative humidity of around 80%, sustained over a period of days, as an indicator of mould risk on moisture-sensitive materials; duration, substrate and temperature all influence whether growth actually occurs. At 20 °C and 50% RH, the dew point is 9.3 °C, but a surface reaches 80% RH already at about 12.6 °C.

Article content

National rules translate this into a minimum temperature factor for thermal bridges: DIN 4108-2 in Germany requires fRsi of at least 0.70, and BRE IP 1/06 in the UK uses 0.75 for dwellings. A detail can therefore meet the condensation criterion at the glass and still fall short of the mould criterion at the surrounding reveal, sill or wall junction.

5. Why New Windows Can Create New Problems

A common complaint after renovation is: “We installed new windows and now we have condensation and mould.” Research shows this is real, but not inevitable.

Old windows leaked. New airtight windows reduce uncontrolled infiltration, which can expose a building whose designed ventilation was never adequate. A study of Polish buildings found that after wooden frames were replaced with airtight plastic ones, air circulation in the flats and ventilation ducts dropped, and damp wall surfaces became infested with mould. In Finland, a deep renovation of a 1968 apartment block improved envelope airtightness by nearly 40%.

Article content

A 2005 UCL study by Davies and colleagues used two methods. Ten dwellings were pressure-tested before and after window replacement, and the measured and predicted results showed that replacement windows can significantly reduce background air exchange. Separately, a telephone survey of 250 households found that only five, or 2%, reported worse condensation afterwards. The study used 0.5 air changes per hour as a reference level for background ventilation, while noting that actual needs depend on occupancy and moisture production. Its conclusion: dwellings with high moisture production and low ventilation are the ones at risk.

Replacing windows therefore also changes how a building is ventilated. Where the old leaks disappear and nothing takes their place, the moisture stays inside.

6. The Installed Façade Performs Differently from the Laboratory Window

A condensation rating describes a window tested on its own. Once installed, its coldest point is often no longer in the window at all, but at the junction with the wall.

The installation junction decides much of the result. A window placed at the outer edge of a masonry wall, outside the insulation plane, leaves the reveal and sill exposed to cold. A window positioned within the insulation layer, with continuous perimeter insulation, keeps the junction warm. Uninsulated mounting brackets, a solid sill that bridges the insulation, and a discontinuous internal airtightness connection each add a local cold spot or a path for humid air. This is especially relevant in the Balkan renovation market, where windows are often replaced without correcting the surrounding wall junction, leaving the original thermal bridge untouched.

Operation changes the result too. Pacific Northwest National Laboratory tested insulating shades and found that when a window is fully covered in winter, less warm room air reaches the glass, so the glass and frame get colder and the risk of internal condensation rises. In building-physics terms, the shade lowers the internal surface heat transfer coefficient and traps an air layer against the glass. This is why people often say “the condensation started after we installed blinds”.

Article content

Curtain walls show the same effect. A case study published by ASTM compared condensation ratings, computer simulations and on-site measurements on a high-rise office, and found that real conditions can change a façade’s condensation resistance. Interior blinds act as an insulator, and spandrel insulation, although necessary for energy performance, can lower the temperature of adjacent framing.

Condensation performance is therefore a property of the installed system and the way it is used, not of the product alone.

7. Can New Glass Technology Prevent Condensation?

Most glazing technologies are passive: they raise internal surface temperatures by reducing heat loss, and shift the condensation threshold by a few degrees. One is active.

Warm-edge spacers. Stainless steel and polymer-composite spacers lower Ψg and can raise the glass-edge temperature by several degrees compared with aluminium, often quoted as 3 to 5 °C, depending on the complete window configuration. The benefit appears only once the frame itself is thermally adequate: a frame without a thermal break can sit at around 3 °C on the inside, and no glass upgrade compensates for that.

Triple glazing. Moving from double low-e glazing (Ug about 1.0 to 1.1 W/m²K) to triple glazing (Ug about 0.5 to 0.7 W/m²K) raises the centre-of-glass surface temperature from about 16 °C to about 18 °C at −5 °C outside. It lowers the risk without removing it, and it increases the frequency of external condensation.

Vacuum insulating glass. Pilkington Spacia uses a 0.2 mm evacuated gap to reach the performance of conventional double glazing in a unit just over 6 mm thick, with current ranges quoted down to about 0.7 W/m²K. It suits heritage and renovation projects that keep original frames; its rigid edge seal is its most sensitive detail.

Article content

Low-e coating on surface 1. Pilkington Anti-Condensation Glass carries a durable pyrolytic coating on the outward-facing surface, reducing long-wave radiation to the night sky. It is designed to delay and, in many cases, prevent external condensation, with no effect on the room side.

Hydrophilic coatings. They do not change the surface temperature. Water still condenses, but spreads into a thin, transparent film instead of light-scattering droplets.

Electrically heated glass. Electrically heated glass is one of the few glazing technologies that can actively maintain a surface temperature above the dew point. Unlike passive insulation improvements, it supplies heat directly to the glass through a transparent conductive coating, allowing the system to respond to changing indoor and outdoor conditions. Manufacturer information gives 50 to 100 W/m² as a typical design range for condensation control; actual needs depend on glass configuration, heat losses, ambient conditions and the control strategy, and above 100 W/m² the glass temperature is regulated with a room thermostat and a sensor in the unit. UK pool projects have used it in place of trench heaters and air curtains. The trade-offs are energy use, electrical installation and controls.

Sunlight-activated coatings (research stage). ETH Zurich has developed a transparent coating about 10 nanometres thick, gold between two titanium oxide layers, that turns the infrared part of sunlight into heat; an earlier version raised surface temperature by 3 to 4 °C. Published in Nature Nanotechnology in 2022, it has been tested on eyewear and plastic films, not façade glass. Façade condensation forms mostly at night and early morning, when there is no sun to drive it.

Passive technologies move the threshold; only active heating can follow the conditions, at the cost of energy and controls.

8. The Swimming Pool Test: Where Façade Design Is Pushed to Its Limits

An indoor pool is the hardest condensation test a glass façade can face.

According to IIBEC, ASHRAE recommends 50 to 60% relative humidity for indoor pools, and in cold climates IIBEC advises staying as close to 50% as possible. At 28 °C and 50% RH, the dew point is already about 17 °C; at 30 °C and 55%, about 20 °C. Compared with an ordinary interior at 21 °C and 50%, that is roughly 700 Pa more vapour pressure. At −5 °C outside, every internal surface, including frames, glass edges and sills, needs an fRsi of roughly 0.7 through the coldest night of winter.

Article content

Standard curtain wall with double glazing reaches only about 8 to 12 °C at the glass edges in those conditions, roughly 10 °C short. Pool enclosures that perform rely on a combination of measures rather than one:

  • triple glazing with warm-edge spacers and a high-performance thermal break
  • warm, dry air supplied along the glass, or electrically heated glass
  • controlled humidity, with the setpoint lowered towards 50% in winter, as dehumidifier manufacturer Dantherm describes
  • air temperature held a few degrees above the water temperature to limit evaporation

Removing any one of these can increase the condensation risk substantially; actual performance depends on the combined design.

So, Can Condensation Be Stopped?

On the room side, in most buildings, yes. Externally, it can be reduced, and it is better read as a sign of well-insulating glass. Between the panes, it can only be prevented, not repaired.

The lesson is simple: neither the lowest U-value nor the newest technology makes a façade condensation-free. What decides it is whether the coldest point of the installed façade stays above the dew point of the building it serves.

Surface temperatures quoted for specific elements are illustrative values for 20 °C inside and −5 °C outside. Values for a specific system come from thermal modelling of that system.